Facebook Login JavaScript Example
3M Construction Assembling & Trading Co., Ltd

THE MORE PROFESSIONAL, THE SAFER!

  • Tiếng Anh
  • Tiếng Việt
+84 903 815 852 - +84 225 3 564 259

Contact us 24/7

119/81 Nguyen Trai street, Ngo Quyen district, Hai Phong city, Vietnam

Our address

“Mid-sized bulk” 6 t to

Views: 2789

An LPG tank is equipped with its safety and operating components with ground conductor. After the gas outlet tank valve:

1 pressure reducing outlet valve 1,5 bars

1 pressure limiter, outlet pressure 1 .75 bars

(The 1 .5 bar pressure at gas regulator outlet can be set at 1 bar or less, which makes it possible to increase the natural vaporisation rate of the tank or tanks.)

X meters of seamless draft steel pipe line, diameter according to flow rate.

3MCO recommendations or IGU** specifications: B 521

If a section of this pipe line must be buried, provide a 0.60 m deep trench and place a plastic yellow screen 30 cm below ground level. (see “trenches” file)

This buried pipe line will be treated against corrosion and stray currents (solacier tube or similar).

Before building entry provide a general stop valve housed in a case.

For the E.R.P. (Premises Open to the Public) provide a “palm button” general emergency stop valve housed in a case outside the building.

Note: If the tank is able to be accessed by the public, provide a chainlink fence and place a “no smoking” sign on each side of the fence together with safety precautions on the front gate of the storage area.

** IGU: International Gas Union

SAFETY PRECAUTIONS and “NO SMOKING” SIGNS

Posting of “no smoking” signs on the four sides of the storage unit to be attached to either the chain-link fence or grounded supports.

Posting of safety precautions with the name and telephone number of installer as well as the telephone number of the civil protection centre.

FIRE PROTECTION

Provide a 9 kg portable dry chemical extinguisher within the storage area.

The tank must be equipped with a spray projection cooling ramp (dry rising main with isolation valve).

ELECTRICAL APPARATUS

All electric equipment located in the safety zone must be explosion-proof.

Dimensions of “mid-sized bulk” tanks from 6 t to

1 “Mid-sized bulk “ tank top view

1 “Mid-sized bulk “ tank side view

2 “Mid-sized bulk “ tanks top view

2 “Mid-sized bulk “ tanks side view